• My Account
  • Shopping Cart
  • Checkout
Call: 1-403-836-0307
Sigineer Power
  • HOME
  • PRODUCTS
    • Inverter Charger
      • 12V Inverter Chargers
      • 24V Inverter Charger
      • 48V Inverter Charger
      • 110V 120V Single Phase Inverter Charger
      • 120 240V Split Phase Inverter Chargers
      • 1000W – 3000W Inverter Charger
      • 4000W – 6000W Inverter Charger
      • 10kW – 20kW Inverter Charger
      • Tesla Battery Compatible Inverter Charger
      • Three Phase Inverter Charger
    • Solar Inverter
      • ETL Listed Inverter to UL1741 CSA22.2
      • Low Frequency Solar Inverter Duty Transformer
      • Off Grid Solar Inverter without Transformer
    • LiFePO4 Battery
      • 19″ Rack Mount Lithium Battery
      • Lithium Ion Battery Home Powerwall
      • Battery Energy Storage System(BESS)
      • 12v Lithium Ion Battery For Car RV
      • 24V Lithium Ferrophosphate Battery
      • 48V Deep Cycle Lithium Battery
    • Accessories
      • Solar Charge Controller
      • Automatic Transfer Switch
      • Power Inverter Accessories
      • Step Up Down Transformer
  • REVIEWS
  • SUPPORT
    • Warranty & After-Sales Service
    • Document Download
    • Software Download
    • Video Gallery
    • FAQ
    • Customer Care
  • APPLICATIONS
    • Off Grid Renewable Energy
    • Recreational Vehicles
    • Utility Work Vehicles
    • Heavy Duty Work Truck & Fleet
    • Residential Commercial
    • Custom Power Inverter Solutions
  • ABOUT
    • Company Overview
    • Affiliate Program
    • Engineering & Technology
    • Wholesale & Distribution
    • Inverter OEM & ODM
    • Certificates
    • Testimonials
    • Blog
  • CONTACT
  • Click to open the search input field Click to open the search input field Search
  • Menu Menu
  • Shopping Cart Shopping Cart
    0Shopping Cart

How to calculate battery capacity for inverter systems

10/27/2016/0 Comments/in Uncategorized/by Sigineer Power

To find out how many batteries for your inverter. The rule  is“maximize run time, minimize the battery size and cost.”

The formula is :

Battery Capacity(WH)*Discharge coefficiency*Inverter efficiency=Load wattage(W) * Runtime(H)

If you know the load watts instead of amps, follow the following procedure

Step A: Convert watts to amps

Actually, watts is the fundamental unit of power and watt-hours is the energy stored. The key is to use the watts you know to calculate the amps at the battery voltage .

For example, say you want to run a 250 watt 110VAC light bulb from an inverter for 5 hours.
Watt-hours = watts * hours = 250 watts * 5 hours = 1250 watt hours

Account for the efficiency of the inverter, say 85%

Watt-hours = watts * hours / efficiency = 1250 / 0.85 = 1470 watt-hours

Since watts = amps * volts divide the watt hours by the voltage of the battery to get amp-hours of battery storage

Amp-hours (at 12 volts) = watt-hours / 12 volts = 1470 / 12 = 122.5 amp-hours.
If you are using a different voltage battery the amp-hours will change by dividing it by the battery voltage you are using.

If you know the amps drawn on battery, follow the following procedure

Step 1. 

If the current drawn from battery is x amps, the time is T hours then the capacity C in amp-hours is

C = xT

For example, if your pump is drawing 120 A and you want it to run for 24 hours

C = 12 Amps * 24 hours = 2880 amp hours

Step 2. Cycle life considerations

It isn’t good to run a battery all the way down to zero during each charge cycle. For example, if you want to use a lead acid battery for many cycles you shouldn’t run it past 80% of its charge, leaving 20% left in the battery. This not only extends the number of cycles you get, but lets the battery degrade by 20% before you start getting less run time than the design calls for

C’ = C/0.8

For the example above

C’ = 2880 AH / 0.8 = 3600 AH

Step 3: Rate of discharge considerations

Some battery chemistries give much fewer amp hours if you discharge them fast. This is called the Peukart effect. This is a big effect in alkaline, carbon zinc, zinc-air and lead acid batteries. For example if you draw at 1C on a lead acid battery you will only get half of the capacity that you would have if you had drawn at 0.05C. It is a small effect in NiCad, Lithium Ion, Lithium Polymer, and NiMH batteries.

For lead acid batteries the rated capacity (i.e. the number of AH stamped on the side of the battery) is typically given for a 20 hour discharge rate. If you are discharging at a slow rate you will get the rated number of amp-hours out of them. However, at high discharge rates the capacity falls steeply. A rule of thumb is that for a 1 hour discharge rate (i.e. drawing 10 amps from a 10 amp hour battery, or 1C) you will only get half of the rated capacity (or 5 amp-hours from a 10 amp-hour battery). Charts that detail this effect for different discharge rate can be used for greater accuracy.

For example, if your portable guitar amplifier is drawing a steady 20 amps and you want it to last 1 hour you would start out with Step 1:

C=20 amps * 1 hour = 20 AH

Then proceed to Step 2

C’ = 20 AH / 0.8 = 25 AH

Then take the high rate into account

C’‘=25 /.5 = 50 AH

Thus you would need a 50 amp hour sealed lead acid battery to run the amplifier for 1 hour at 20 amps average draw.

Step 4. What if you don’t have a constant load? The obvious thing to do is the thing to do. Figure out an average power drawn. Consider a repetitive cycle where each cycle is 1 hour. It consists of 20 amps for 1 second followed by 0.1 amps for the rest of the hour. The average current would be calculated as follows.

20*1/3600 + 0.1(3599)/3600 = 0.1044 amps average current.

(3600 is the number of seconds in an hour).

In other words, figure out how many amps is drawn on average and use steps 1 and 2. Step 3 is very difficult to predict in the case where you have small periods of high current. The news is good, a steady draw of 1C will lower the capacity much more than short 1C pulses followed by a rest period. So if the average current drawn is about a 20 hour rate, then you will get closer to the capacity predicted by a 20 hour rate, even though you are drawing it in high current pulses. Actual test data is hard to come by without doing the test yourself.

Share this entry
  • Share on Facebook
  • Share on X
  • Share on WhatsApp
  • Share on Pinterest
  • Share on LinkedIn
  • Share on Tumblr
  • Share on Vk
  • Share on Reddit
  • Share by Mail
https://sigineer.com/wp-content/uploads/2023/09/SG-Logo-H70.jpg 0 0 Sigineer Power https://sigineer.com/wp-content/uploads/2023/09/SG-Logo-H70.jpg Sigineer Power2016-10-27 10:17:002020-11-19 09:05:47How to calculate battery capacity for inverter systems
0 replies

Leave a Reply

Want to join the discussion?
Feel free to contribute!

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

This site uses Akismet to reduce spam. Learn how your comment data is processed.

Search Search

CATEGORIES

  • Blog
  • Features
  • Markets
  • News
  • Uncategorized
  • Video

RECENT COMMENTS

    LATEST NEWS

    • UL Listed Inverter Charger
    • AC Coupled Inverter Charger
    • Sigineer Power Launches Off Grid 4KW to 12KW Solar Inverters UL1741 & CSA 22.2 Certified to the United States & Canadian Markets
    • RV INVERTER INSTALLTION INSTRUCTIONS
    • AGS for M series Solar Inverters

    ARCHIVE

    • August 2023
    • May 2022
    • January 2022
    • July 2021
    • April 2021
    • January 2021
    • November 2020
    • February 2020
    • October 2018
    • August 2018
    • October 2017
    • May 2017
    • April 2017
    • March 2017
    • January 2017
    • October 2016
    • September 2016
    • August 2016
    • July 2016
    • June 2016

    TAGS

    power inverter Philippines Sine converter single phase inverter sinusoidal inverter Stackable Power Inverter UL458 inverter ultimate power inverter Whole House Inverter

    COLLECTIONS

    • Inverter Charger
    • Solar Inverter
    • LiFePO4 Battery
    • Solar Charger
    • Accessories

    CUSTOMER CARE

    • PRIVACY POLICY
    • SHIPPING POLICY
    • RETURN & REFUND POLICY
    • TERMS AND CONDITIONS
    • INTELLECTUAL PROPERTY RIGHTS

    CONTACT US

    • Email: info@sigineer.com
    • Phone: +14038360307
    • Skype: sigineer@outlook.com

    ABOUT US

    • INTRODUCTION
    • DISTRIBUTORS
    • TESTIMONIALS
    • FAQ
    • AFFILIATE PROGRAM
    © Copyright 2025 - Sigineer Power
    • Link to Facebook
    • Link to X
    • Link to Flickr
    • Link to Youtube
    Link to: Why Inverter Overload Capability Matters So Much For Inductive Loads? Link to: Why Inverter Overload Capability Matters So Much For Inductive Loads? Why Inverter Overload Capability Matters So Much For Inductive Loads? Link to: Purchase Advanced 12kw Inverter to Support Your Large Mobile Power Units Link to: Purchase Advanced 12kw Inverter to Support Your Large Mobile Power Units Purchase Advanced 12kw Inverter to Support Your Large Mobile Power Units
    Scroll to top Scroll to top Scroll to top